Skip links

Heat Shrink Bus Bar Sleeve

Home / Heat Shrink Bus Bar Sleeve

Bus Sleeve is heat shrinkable busbar Sleeve designed to insulate busbar system up to 36kV & to protect against accidental flash-over. The Sleeve are manufactured from high quality cross-linked polyolefin material. Meet ANSI C37.20.2 standard for MV switchgear application up to 36kV.

Features & Benefits

Applications

Diagram

Selection Chart – Thin Wall Tube [Up to 3.3KV]

Selection Chart
Thin Wall Tube [Up to 3.3KV]
Gala Size D d T (±10%) Reel Length Rectangular Bars (W+B) Round Bar Ø mm
mm (min.) mm (max.) mm mtrs Min. Max. Min. Max.
GSC 16/8 16 8 0.69 100 16 18 12 12
GSC 20/10 20 10 0.78 100 22 25 14 16
GSC 30/15 30 15 0.86 50 33 38 21 24
GSC 40/20 40 20 0.96 50 44 52 28 33
GSC 50/25 50 25 0.96 25 53 65 34 41
GSC 60/30 60 30 0.96 25 64 75 41 48
GSC 70/35 70 35 1.10 25 72 90 46 57
GSC 80/40 80 40 1.27 25 86 100 55 64
GSC 100/50 100 50 1.40 25 104 125 66 80
GSC 120/60 120 60 1.40 25 110 150 70 96
GSC 150/75 150 75 1.40 25 151 190 96 121
GSC 180/90 180 90 1.50 25 179 236 114 150

Selection Chart – Medium Wall Tube [Upto 24KV]

Selection Chart
Medium Wall Tube [Upto 24KV]
Gala Size D d T (±10%) Reel Length Rectangular Bars (W+B) Round Bar Ø mm
mm (min.) mm (max.) mm mtrs Min. Max. Min. Max.
GMB 16/6 16 6 1.70 25 11 18 7 12
GMB 25/10 25 10 2.50 25 16 30 12 20
GMB 30/12 30 12 2.10 25 25 38 16 25
GMB 40/16 40 16 2.10 25 33 50 21 32
GMB 50/20 50 20 2.10 25 38 63 24 40
GMB 65/25 65 25 2.20 25 53 82 34 52
GMB 75/28 75 28 2.50 25 63 94 40 60
GMB 85/32 85 32 2.50 25 69 107 44 68
GMB 100/38 100 38 3.00 25 83 126 53 80
GMB 120/45 120 45 3.00 25 104 150 66 96
GMB 150/60 150 60 3.30 20 132 200 84 127
GMB 180/72 180 72 3.00 15 151 226 96 144
GMB 205/85 210 84 3.10 1.5 239 257 152 164
GMB 250/100 250 100 3.10 1.5 264 314 168 200

Selection Chart – Heavy Wall Tube [upto 36KV]

Selection Chart
Heavy Wall Tube [upto 36KV]
Gala Size D d T (±10%) Reel Length Rectangular Bars (W+B) Round Bar Ø mm
mm (min.) mm (max.) mm mtrs Min. Max. Min. Max.
GHB 25/8 25 8 3.20 25 20 28 13 20
GHB 30/12 30 12 3.50 25 28 33 18 25
GHB 40/16 40 16 3.50 25 35 45 22 32
GHB 50/20 50 20 3.50 25 45 54 29 40
GHB 65/25 65 25 3.50 25 50 62 32 43
GHB 75/28 75 28 3.50 20 53 69 34 47
GHB 85/32 85 32 3.50 20 69 100 44 68
GHB 100/38 100 38 3.70 20 83 102 53 72
GHB 120/45 120 45 3.70 20 94 125 60 85
GHB 150/60 150 60 3.70 15 122 168 78 105
GHB 180/70 180 70 3.70 15 160 196 102 125
GHB 205/85 205 85 3.70 1.5 239 250 152 164
GHB 250/120 250 120 4.20 1.5 264 314 168 200

Technical Specification

Technical Specification
Test DescriptionRecorded ValueTest Method
Physical
Tensile Strength9 N/mm² (MPA)(min.)ASTM D638
Ultimate Elongation350% (min.)ASTM D638
Water Absorption0.5 % (max.)ASTM D570
Density1.20 ± 0.2 gm/cm³ASTM D792
Hardness45 ± 10 Shore DASTM D2240
Thermal
Accelerated Ageing(150°C for 1200 Hrs)IEC 60684-2
Tensile Strength7.7 N/mm² (Mpa)ASTM D 638
Ultimate Elongation300 % (Min.)ASTM D638
Low Temperature Flexibility (-40°C for 4 Hrs.)No CrackingASTM D2671
Heat Shock (250°C for 30 Min.)No Cracking or flowingESI 09-11
Shrink Temperature125°CIEC 216
Continuous Temperature limit-40°C to +115°CIEC 216
Electrical
Dielectric Strength22 KV/mm. (Min.)ASTM D149
Volume Resistivity1 x 10¹³ Ohm.cm (min.)ASTM D257
Dielectric Constant5 (Max.)ASTM D150

Clearance With Insulation

Clearance With Insulation
Voltage Medium Wall Tube (GMB) Heavy Wall Tube (GHB) Un-Insulated Busbars (mm) as per IEC 71-2
PH to PH (mm) PH to GR (mm) PH to PH (mm) PH to GR (mm)
Rectangular Round Rectangular Round Rectangular Round Rectangular Round
12 kV 65 55 57 65 35 30 45 40 120
17.5 kV 85 70 105 85 55 50 65 60 160
24 kV 115 95 150 125 70 60 100 90 220
36 kV 200 150 285 205 140 130 190 180 320

Certificates

FAQs

1. What is a Heat Shrink Shroud?

A Heat Shrink Shroud is a protective sleeve made from cross-linked polymer material that shrinks when heat is applied. It provides insulation, sealing, and mechanical protection for cables, joints, and terminations.

When heat is applied using a heat gun or torch, the shroud shrinks uniformly and tightly wraps around the cable or joint, creating a secure and sealed covering.

When heat is applied using a heat gun or torch, the shroud shrinks uniformly and tightly wraps around the cable or joint, creating a secure and sealed covering.

It is typically made from cross-linked polyolefin material, often containing carbon black for UV resistance and weather protection.