Skip links

Overhead Line Cover - Silicone - Self-locking

Home / Overhead Line Cover – Silicone – Self-locking

Gala Silicon Overhead Line Covers are made from high quality non-tracking silicon rubber that are designed for field installation over bare conductors. These covers provide a layer of electrical insulation for Phase-to-Phase and Phase-to-Ground protection from bird and animals. The GSOC provides electrical insulation, UV resistance and tracking resistance. Silicon Self-fusing Tape can be applied on it for better insulation.

Features and Benefits

Diagram

Selection Chart – GSOC-M (Upto 12kV)

Selection Chart – GSOC-M (Upto 12kV)

Gala CodeConductor Dia. (mm)Thickness (mm)Packaging (Mtr./Roll)
GSOC-M 15Up to 152.015
GSOC-M 20Up to 202.015
GSOC-M 24Up to 242.015
GSOC-M 32Up to 322.015
GSOC-M 38Up to 382.015

Selection Chart – GSOC-H ( Upto 36kV )

Selection Chart – GSOC-H (Upto 36kV)
Gala Code Conductor Dia. (mm) Thickness (mm) Packaging (Mtr./Roll)
GSOC-H 15 Up to 15 2.7 15
GSOC-H 20 Up to 20 2.7 15
GSOC-H 24 Up to 24 2.7 15
GSOC-H 32 Up to 32 2.7 15
GSOC-H 38 Up to 38 2.7 15

Selection Chart – GSOC – H3 ( Upto 36kV )

Technical Specification
PROPERTIES TEST METHOD TYPICAL VALUE
Physical
Tensile Strength ASTM D638 7 N/mm² (Min.)
Elongation ASTM D638 300% (min)
Water Absorption ASTM D570 0.5 (Max)
Low Temp. Install at 0°C Installable without difficulty
Longitudinal Change -10% (Max.) ASTM D638
Thermal
Air Ageing ASTM D2671 150°C for 168 hrs.
Tensile Strength ASTM D638 3.5 N/mm² (Min.)
Elongation ASTM D638 150% (Min.)
Electrical
Di-electric Strength ASTM D149 >210 kV / cm
Volume Resistance ASTM D257 1×10 13 Ohm cm (Min)
Tracking and Erosion Resistance ASTM D2303 No tracking or erosion to top surface or flame failure after
1 hr. at 2.5 kV
1 hr. at 2.75 kV
1 hr. at 3.0 kV
20 min. at 3.25 kV

* The above mentioned values are typical analytical values obtained on material when tested as per applicable standards under controlled laboratory conditions and should not be construed as Specifications for the product.

Selection Chart GSOC-EH (Upto 765kV)

Selection Chart GSOC-EH (Upto 765kV)
Gala Code Conductor Dia. (mm) Thickness (mm) Packaging (Mtr./Roll)
GSOC-EH-15 Up to 15 5.0 15
GSOC-EH-20 Up to 20 5.0 15
GSOC-EH-24 Up to 24 5.0 15
GSOC-EH-32 Up to 32 5.0 15
GSOC-EH-38 Up to 38 5.0 15

Technical Specification

Technical Specification*
PROPERTIES TEST METHOD TYPICAL VALUE
Physical
Tensile Strength ASTM D638 4 N/mm² (Min.)
Elongation ASTM D638 200% (Min.)
Density ASTM D792 1.10 – 1.45 gm/cm³
Hardness ASTM D2240 65 ± 5 Shore A
Low Temp. Flexibility (-20°C / 4 Hrs.) ASTM D2671 No Cracking
Water Absorption (24 Hrs @ 23°C) ASTM D570 0.5% (Max.)
Thermal
Thermal Ageing ASTM D2671 150°C for 168 Hrs.
Tensile Strength (After Ageing) ASTM D638 3 N/mm² (Min.)
Elongation (After Ageing) ASTM D638 100% (Min.)
Electrical
Dielectric Strength ASTM D149 21 kV/mm (Min.)
Volume Resistance ASTM D257 1 × 10¹⁰ Ohm·cm (Min.)
Tracking & Erosion Resistance ASTM D2303 No tracking or erosion to top surface or flame failure after:
• 1 hr at 2.5 kV
• 1 hr at 2.75 kV
• 1 hr at 2.5 kV
• 1 hr at 3.0 kV
• 20 min at 3.25 kV

* The above mentioned values are typical analytical values obtained on material when tested as per applicable standards under controlled laboratory conditions and should not be construed as product specifications.

Related Products

Untitled design (6)

Polyolefin Overhead Line Cover

Untitled design (4)

Polyolefin Overhead Line Cover

4CD9TxZovDj2ZAlbOb0QfWVY0RAyZA-removebg-preview

Polyolefin Overhead Line Cover

109+

Countries

Served

40+

Years

In Industry

1250+

Kw

Solar Generative

225000

Area

Sq ft

This site is registered on portal.liquid-themes.com as a development site. Switch to production mode to remove this warning.