Bus Bar Insulating Shrouds Polyolefin

Home / Bus Bar Insulating Shrouds Polyolefin

Busboot – Polyolefin is flexible electrical insulating boot / shroud for busbar and switchgear connections upto 36KV. These pliable boots can be installed, removed or replaced in few minutes. Made from high quality Cross-linked Polyolefin material to provide excellent electrical insulation and to withstand higher operating temperature continuously
It provides reduction in air clearance, which helps designing compact panels; thereby reduces the material costs by saving in busbar lengths, sheet metal components, etc.

Features and Benefits

Selection Chart

Selection Chart
VoltageThickness
12.0 kV1.0 mm
18.0 kV1.4 mm
24.0 kV1.8 mm
36.0 kV2.5 mm

Technical Specification

Technical Specification
Test Description Recorded Value Test Method
Physical
Tensile Strength 9 N/mm² (MPa) (min.) ASTM D638
Ultimate Elongation 300% (min.) ASTM D638
Water Absorption 0.5% (max.) ASTM D570
Hardness 45 ± 10 Shore D ASTM D2240
Thermal
Low Temperature Flexibility (-40°C for 4 Hrs.) No Cracking ASTM D2671
Heat Shock (90°C for 30 Min.) No Cracking or flowing ESI 09-11
Continuous Temperature Limit -40°C to +115°C IEC 216
Electrical
Dielectric Strength 22 kV/mm. (min.) ASTM D149
Volume Resistivity 1 x 10¹³ Ohm.cm (min.) ASTM D257
Dielectric Constant 5 (max.) ASTM D150

Certificates

FAQs

1. What is a Screened Separable Connector?

A Screened Separable Connector is a medium-voltage cable accessory used to connect power cables to transformers, switchgear, or other equipment. It is fully screened and separable, allowing safe installation, disconnection, and maintenance.

They are commonly used for 3.6 kV to 36 kV medium-voltage applications, depending on the connector design and standards.