Heat Shrink Moulded Sealing Caps
Home / Heat Shrink Moulded Sealing Caps
Products
- Heat Shrinkable Joints & Terminations
- Insulation Enhancement Product
- Screened Separable Connectors
- Heat Shrinkable Moulded Shapes
-
Heat Shrink Tubes / Sleeves
- Advantages Of Heat Shrink Tubing
- Thin Wall Tubes
- GDW : Dual Wall Tubing
- Medium/Heavy Wall Tubes-Commercial
- Heat Shrink Co-extruded Tubing Premium Quality
- Red Insulation Tubes
- Non Tracking Tubes
- Busbar Sleeves
- Stress Control Tube
- Non Tracking Tubes
- Integrated Stress Control Tube-GVOT Tube
- Heat Shrink Double Layer Tube-GDTL Tube
- High Shrink Ratio Heat Shrink Tube
-
Switchgear Insulation Products
- Barrier Board Sheet
- End Sealing Kit for Extensible RMU/GIS Bushing
- Heat Shrink Bus Bar Sleeve
- Bus Bar Insulating Shrouds
- Bus Bar Insulating Shrouds Polyolefin
- Bus Bar End Caps
- Thin wall tube wire marking
- Heat Shrink Tape (Bustape)
- Insulation for Circuit Breakers
- Busbar Sleeve for 66 kV
- Bushing Boot
- Non Shrinkable High Voltage Tape
- Heat Shrinkable Gland
- Cable Sealing & Repair Products
- Silicone Overhead Line Cover
- Polyolefin Overhead Line Cover (Insulcover)
- Overhead Line Tube (Insulcover)
- Pipeline / Corrosion / Cathodic Protection Products
- Pole Protection Products
- Wire Harness Products
- New Products
- Miscellaneous
Cable End Caps - Cable End Sealing Cap - INSULCAP
❮
❯
×
Insulcap is used seal the ends of all types of Cables & protect from ingress of water / moisture. The caps are manufactured from high quality cross linked polyolefin material. Compatible with most commonly used Cable Jackets i.e. XLPE, PVC, PILC OR Rubber Sheathed Cable.
Hot Melt adhesive lining provides permanent seal on irregular cable sheaths.
Excellent resistance to weathering, moisture, contamination and adverse environmental conditions, according to IP 68 (Ingress Protection.)
- Temper Proof Application : Custom Logo / Print with special non-removable Ink marks permanent seal in End Cap after shrinking, thereby avoiding claims is case of Pilferage of Cable length.
- Valved End caps (v) available for pressurized application for Telecom cables.
- Special Relief valved End Caps (RV) available for degassing application in High Voltage Power cables.
- Live End Cap Kit available for sealing Live Cables.
- Conductive End Caps are available with Conductive Mastic.
SELECTION CHART
| CODE NO. | Ds (Min.) | Df (Max.) | LS (Min.) | Tf(± 10%) | CABLE RANGE |
|---|---|---|---|---|---|
| GEC 001S | 6 | 2 | 25 | 2.0 | 2.5-4 |
| GEC 001 SA | 8 | 2 | 25 | 2.0 | 2.5-6 |
| GEC 001 | 12 | 4 | 40 | 2.3 | 5-8 |
| GEC 001 L | 12 | 4 | 58 | 2.3 | 5-8 |
| GEC 001 A | 14 | 4 | 40 | 2.3 | 5-11 |
| GEC 001A L* | 14 | 4 | 58 | 2.3 | 5-11 |
| GEC 101 | 20 | 7.5 | 55 | 2.3 | 10-16 |
| GEC 101 L | 20 | 8 | 75 | 2.5 | 10-16 |
| GEC 101 A | 25 | 8 | 55 | 2.3 | 10-20 |
| GEC 101 A L | 25 | 8 | 75 | 2.5 | 10-20 |
| GEC 102 | 30 | 11 | 75 | 2.5 | 13-26 |
| GEC 102 L* | 30 | 11 | 110 | 2.5 | 13-26 |
| GEC 102 A | 35 | 11 | 75 | 2.5 | 13-30 |
| GEC 102 A L* | 35 | 11 | 115 | 2.5 | 13-30 |
| GEC 201 | 40 | 15 | 90 | 3.3 | 17-35 |
| GEC 201 L | 40 | 15 | 120 | 3.3 | 17-35 |
| GEC 201 A | 45 | 15 | 90 | 3.3 | 17-40 |
| GEC 201 AL | 45 | 15 | 120 | 3.3 | 17-40 |
| GEC 301 | 55 | 25 | 125 | 3.5 | 30-47 |
| GEC 301 L | 55 | 25 | 170 | 3.5 | 30-47 |
| GEC 301 A | 63 | 25 | 125 | 3.5 | 30-55 |
| GEC 301 AL | 63 | 25 | 170 | 3.5 | 30-55 |
| GEC 401 | 75 | 35 | 140 | 4.0 | 42-68 |
| GEC 401 L | 75 | 35 | 180 | 4.0 | 42-68 |
| GEC 401 A | 85 | 36 | 140 | 4.0 | 42-78 |
| GEC 401 AL* | 85 | 35 | 180 | 4.0 | 42-78 |
| GEC 501 | 100 | 45 | 160 | 4.0 | 55-90 |
| GEC 501 L | 100 | 45 | 200 | 4.0 | 55-90 |
| GEC 501 A | 120 | 45 | 160 | 4.0 | 55-110 |
| GEC 501 AL | 120 | 45 | 200 | 4.0 | 55-110 |
| GEC 601 | 130 | 60 | 160 | 4.6 | 75-120 |
| GEC 601 L | 130 | 65 | 300 | 4.6 | 75-120 |
| GEC 701 | 158 | 60 | 165 | 4.6 | 75-145 |
| GEC 701 N | 158 | 65 | 165 | 5.5 | 75-145 |
| GEC 701 L | 160 | 65 | 300 | 4.5 | 75-120 |
| GEC 701 AL | 170 | 65 | 300 | 4.5 | 75-145 |
| GEC 701 XXL | 160 | 75 | 585 | 3.8 | 85-160 |
| GEC 801 S* | 190 | 125 | 220 | 4.0 | 140-165 |
| GEC 801 | 230 | 125 | 220 | 4.0 | 140-200 |
| GEC 801 A | 280 | 125 | 225 | 3.8 | 140-250 |
| GEC 801 AL | 280 | 125 | 550 | 3.8 | 140-250 |
| GEC 901 | 310 | 120 | 220 | 7.0 | 140-280 |
| GEC 1001 | 400 | 204 | 220 | 6.0 | 230-360 |
| GEC 1101 | 500 | 204 | 220 | 6.0 | 230-460 |
D : Internal Diameter ; s : as supplied ; f : after free recovery
TECHNICAL SPECIFICATION
| PROPERTIES | VALUE | STANDARD |
|---|---|---|
| Physical | ||
| Tensile Strength | 12 N/mm² (MPA)(min.) | ASTM D638 |
| Ultimate Elongation | 350% (Min.) | ASTM D638 |
| Density | 1.05 ± 0.2 gm/cm³ | ASTM D792 |
| Hardness | 45 ± 10 Shore D | ASTM D2240 |
| Water Absorption | 0.2 % (max.) | ASTM D570 |
| Thermal | ||
| Accelerated Ageing | (120°C for 500 Hrs) | ASTM D2671 |
| Tensile Strength | 11 N/mm² (Mpa) (min.) | ASTM D 638 |
| Ultimate Elongation | 300% (Min.) | ASTM D638 |
| Low temperature Flexibility (-40°C for 4 Hrs.) | No Cracking | ASTM D2671 |
| Heat Shock (250°C for 30 Min.) | No Cracking or flowing | ESI 09-11 |
| Shrink Temperature | 125°C | IEC 216 |
| Continuous Temperature Limit | -40°C to + 110°C | IEC 216 |
| Electrical | ||
| Dielectric Strength | 12 KV/mm. (Min.) | ASTM D149 |
| Volume Resistivity | 1 x 10¹⁴ Ohm.cm(min.) | ASTM D257 |
| Dielectric Constant | 5 (Max.) | ASTM D150 |
109+
Countries
Served
40+
Years
In Industry
1250+
Kw
Solar Generative
225000
Area
Sq ft