Test Specifications

Home / Test Specifications

Technical Specifications

Guaranteed Technical Particulars in compliance with IEC 60502-4 & CENELEC HD 629.1

Test SequenceParameter for
Evaluation
Test Voltage Highest Voltage Umax (kV)Result
  122436 
DC High Voltage Test (Dry)15 min.3876114No breakdown & no flashover
AC High Voltage Test (Wet) (Only for OD Terminations)1 Min.25.45176No breakdown & no flashover
Partial Discharge Test112233= 5 pC
Insulation Resistance (Before Impact Test)1 min. 500 V DC>10³ Ω
Impact Test (For Straight Through Joints)PASS (No visual damage observed)
Insulation Resistance After Impact Test (Immersed)1 min. 500 V DC>10³ Ω
Impulse Withstand Test at Elevated Temperature10 Positive & 10 Negative
Conductor temperature 95 to 100°C
95125170No breakdown & no flashover
Heating Cycle Test in Air3 cycles 5 hrs heating & 3 hrs cooling16 AC30 AC45 ACNo breakdown & no flashover
Partial Discharge Test at Elevated TemperatureConductor temperature 95 to 100°C112233= 5 pC
Partial Discharge Test at Ambient Temperature112233= 5 pC
Heating Cycle Test in Air (Indoor & Outdoor Termination)60 cycles, 5 hrs heating & 3 hrs cooling16 AC30 AC45 ACNo breakdown & no flashover
Heating Cycle Test in Water (Straight Through Joint)63 cycles, 8 hour cycle (5 hrs heating & 3 hrs cooling)16 AC30 AC45 ACNo breakdown & no flashover
Immersion Test (Outdoor Termination)10 cycles, 5 hr heating & 3 hr coolingNo breakdown & no flashover
Partial Discharge Test at Elevated Temperature5 hr heating & 3 hr cooling, 95 to 100°C112233= 5 pC
Partial Discharge Test at Ambient Temperature112233= 5 pC
Impulse Withstand Test at Ambient Temperature10 Positive & 10 Negative95 Peak125 Peak170 PeakNo breakdown & no flashover
AC High Voltage Test (Dry)15 min.163045No breakdown & no flashover
ExaminationPASS (No cracking, no moisture path, no corrosion or tracking)
DC High Voltage Test (Dry)15 min.3876114No breakdown & no flashover
AC High Voltage Test (Dry)5 min.295786No breakdown & no flashover
Thermal Short-Circuit TestTwo short-circuits to raise conductorsNo visible damage
Impulse Withstand Test at Ambient Temperature10 Positive & 10 Negative95 Peak125 Peak170 PeakNo breakdown & no flashover
AC High Voltage Test (Dry)15 min.163045No breakdown & no flashover
ExaminationPASS (No cracking, no moisture path, no corrosion or tracking)
Humidity Test for Indoor TerminationsWater conductivity 70±0.1 mS/m, 300 hr spray8 AC16 AC24 ACPASS (No breakdown, tracking, erosion or mechanical damage)
Salt Fog Test for Outdoor TerminationsSalt spray for 1000 hours (1.25 x Uo)7.9415.8723.75PASS (No breakdown, tracking, erosion or mechanical damage)
Guaranteed Technical Particulars in compliance with IEC 60502, 60060 & 60230 For Termination upto 3.3 kv

Test SequenceParameter for
Evaluation
Test Voltage Highest Voltage Umax (kV)Result
  1.13.3 
Insulation Resistance1 min. 500 V DC> 10³ Ω
AC High Voltage Test (Dry)15 min.48No breakdown & no flashover
Impulse Withstand Test at Ambient Temperature10 Positive & 10 Negative812No breakdown & no flashover
Heating Cycle Test63 cycles, 8 Hour Cycle, 5 hrs heating & 3 hrs coolingNo breakdown & no flashover
Insulation Resistance After Impact Test (Immersed)1 min. 500 V DC> 10³ Ω
Impulse Withstand Test at Elevated Temperature10 Positive & 10 Negative (Conductor temperature 95°C to 100°C)812No breakdown & no flashover
Heating Cycle Test63 cycles, 8 Hour Cycle, 5 hrs heating & 3 hrs coolingNo breakdown & no flashover
DC High Voltage Test (Dry)5 min.1521No breakdown & no flashover
Guaranteed Technical Particulars in compliance with IEC 60502, 60060 & 60230 For Straight Through Joints upto 3.3 kv
Test Sequence Parameter for Evaluation Test Voltage Highest Voltage Umax (kV) Result
1.1 3.3
Insulation Resistance 1 min. 500 V DC > 10³ Ω
AC High Voltage Test (Joint immersed in water) 15 min. 3.5 6 No breakdown & no flashover
Impulse Withstand Test at Ambient Temperature 10 Positive & 10 Negative 8 12 No breakdown & no flashover
Insulation Resistance 1 min. 500 V Dc > 10³ Ω
Heating Cycle Test in Water (for Straight Through Joint) 63 cycles, 5 hrs. heating & 3 hrs. cooling Conductor temperature 95o No breakdown & no flashover
Insulation Resistance After Impact Test (Immersed) 1 min. 500 V Dc > 10³ Ω
Impulse Withstand Test at Elevated Temperature 10 Positive& 10 Negative Conductor temperature 95 to 100oC 8 12 No breakdown & no flashover
DC High Voltage Test (Dry) 5 min. 15 21 No breakdown & no flashover